Emerson VSS Air Compressor User Manual


 
Suction
Gas
Strainer
Stop
Va l v e
Check
Va l v e
Manually Shut Off Valve to Oil Filter
Manually Open Valve
Run Oil Pump for a minimum
of 5 Minutes and as long as
needed to purge all gas from
oil cooler and piping.
Shut Oil Pump Off.
Open Valve to Oil Filter.
Close Valve #3.
Verify Oil is in Separator
!
"
#
$
%
Follow the Steps Below:
Note: Bottom Site Glass Should Be Full.
Pre Start Up for Proper Oil Separator Level and to Prime the Cooler
Remote Coolers Only
Shows the Flow for Priming the Oil Cooler (Steps 1-5)
Shows the Flow for Priming the Compressor Prior to
Start Up (Steps 6-11)
Very Important: Piping of the oil must enter the
bottom connection of the oil cooler and leave
the top connection.
WARNING: Failure to Follow These Steps Will Result in
Bearing Damage and Compressor Seizing and Will Void
Any and All Warranties That May Apply.
IMPORTANT! FOR REMOTE OIL COOLERS ONLY. READ BEFORE PROCEEDING.
SG
Ball Valve
=
Metering Valve
Manually Close 2a
=
Open Valve 2a
 =