Lincoln Electric SVM188-A Welder User Manual


 
INSTALLATION
A-2 A-2
DC-600
Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOC
Return to Master TOC Return to Master TOC Return to Master TOC Return to Master TOC
60% Duty Cycle
122/61
122/61/49
61
49
128/74/64
74/56
64
140/70
68
TECHNICAL SPECIFICATIONS – DC-600
Volts at Rated Amperes
44
44
44
Auxiliary
Power
See the OPERATION section
for Auxiliary Power
information by model
Amps
600
680
750
Maximum Open Circuit Voltage
72V for 60 HZ models
69V for 50/60 HZ models
Duty Cycle
100% Duty Cycle
60% Duty Cycle
50% Duty Cycle
Output Range
70A/13V-780A/44V (CV)
90A/24V-780A/44V (CC)
INPUT - THREE PHASE ONLY
OUTPUT
1
Also called “inverse time” or “thermal/magnetic” circuit breakers; circuit breakers which have a delay in tripping action that decreases as the magnitude of the current increases.
RECOMMENDED INPUT WIRE AND FUSE SIZES
Standard
Volatge
230/460/60
230/460/575/60
460/60
575/60
220/380/440/50/60
380/500/50/60
440/50/60
200/400/50/60
415/50/60
100% Duty
Cycle
108/54
108/54/43
54
43
116/67/58
67/51
58
128/64
61
50% Duty Cycle
134/67
134/67/54
67
54
138/80/69
80/61
69
152/76
73
Input Current at Rated Output
RATED OUTPUT
INPUT
VOLTAGE /
FREQUENCY
230
460
575
200
220
380
400
415
440
500
TYPE 75°C
(SUPER LAG)
OR BREAKER
SIZE (AMPS)
1
175 Amp
90 Amp
70 Amp
175 Amp
175 Amp
100 Amp
100 Amp
100 Amp
90 Amp
80 Amp
TYPE 75°C
GROUND WIRE
IN CONDUIT
AWG(IEC-MM
2
)SIZES
6 (14)
8 (8.4)
8 (8.4)
6 (14)
6 (14)
8 (8.4)
8 (8.4)
8 (8.4)
8 (8.4)
8 (8.4)
TYPE 75°C
COPPER WIRE
IN CONDUIT
AWG(IEC-MM
2
)SIZES
30°C (86°F) Ambient
2(34)
6(14)
8 (8.4)
1(43)
2(34)
6(14)
6(14)
6(14)
6(14)
8 (8.4)
INPUT AMPERE
RATING ON
NAMEPLATE
108
54
43
128
116
67
64
61
58
51
HERTZ
60
60
60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
PHYSICAL DIMENSIONS
HEIGHT
30.75 in
781 mm
WIDTH
22.25 in
567 mm
DEPTH
39.0 in
988 mm
WEIGHT
522 lbs.
237 kg.