Xantrex Technology PS2.5 Battery Charger User Manual


 
Prosine 2.5/3.0 Installation & Operation Guide 89
Appendix C: Troubleshooting
Error Code Table
The following table lists the error codes, likely causes, and suggested solutions.
Error
Code
Description of Fault Possible Cause Solution
000, 255 No Fault recorded
No faults detected since the
Prosine was turned on.
001 A. Battery Temperature is
too high or too low. (This
code only applies if the
external battery tempera-
ture sensor is connected)
B. If there is no external
battery temperature sen-
sor, there may be a wiring
fault inside the unit.
1. Room temperature around
the batteries is too high or
too low.
2. Battery heating (battery or
battery terminals are
warmer than room tempera-
ture
3. Faulty connection of battery
temperature probe.
B. Damage has likely
occurred during shipping or
there has been extreme
shock or vibration.
1. Keep the temperature
around batteries moder-
ate. In cold weather, try a
battery heating blanket.
In warm weather, try
improving the ventilation.
2. For flooded batteries,
check the electrolyte level
and top up with distilled
water if necessary. Check
the tightness of all con-
nections. If the condition
persists, the battery may
be faulty and need
replacement.
3. Check connections and
make sure probe is in
good thermal contact with
battery. Probe may
require replacement.
B. Record the error code
and contact Xantrex.