Sun Microsystems 6800/4810/4800/3800 Welding System User Manual


 
Chapter 3 System Controller Alphabetical Command Reference 77
max All system board components are tested with all tests
and test patterns. This is the same as default.
mem1 Runs all tests at the default level plus more
exhaustive DRAM and SRAM test algorithms. These
tests take a long time to run.
mem2 This is the same as mem1 with the addition of a
DRAM test that does explicit compare operations of
the DRAM data. These tests take a long time to run.
verbosity-level off No status messages are displayed. POST output is
always displayed. However, with the value set to
off, there is very little POST output displayed and
there may be a long time between output displays.
This depends on your hardware configuration and
the setting of diag-level.
min (default value) Test names status messages, and error messages are
displayed.
max Subtest trace messages are displayed.
error-level off No error messages are displayed.
min The failing test name is displayed.
max (default value) All relevant error status is displayed.
interleave-scope within-cpu The memory banks on a CPU will be interleaved
with each other. Each CPU may have up to four
logical memory banks.
within-board (default
value)
The memory banks on a system board will be
interleaved with each other.
across-boards The memory will be interleaved on all memory
banks across all of the boards in the domain.
With this value, you cannot remove a CPU/Memory
board from the system using DR.
interleave-mode optimal (default value) The memory is mixed-size interleaving in order to
gain optimal performance.
fixed The memory is fixed-size interleaving.
off There is no memory interleaving.
reboot-on-error false (default value) The domain will be paused when the system
controller detects a hardware error.
TABLE 3-10 Parameter Values for the setupdomain Command (Continued)
Parameter Value Description