Power Connections
DC Supply and Motor Cables
The power cables are connected to terminals DC+ and DC- (R+/B+ and DC terminals when
using an external charging circuit) and the motor cables to terminals U, V and W. A cable
entry gland should be used at the motor cable end to reach the EMC levels, see Table 3-2.
Use cables with a heat resistance of at least +60C. The cables and the fuses must be sized
according to the inverter nominal output current which you can find on the rating plate.
Installation of cables according to UL regulations is presented on Page 3-17 and aR fuse sizes
in Tables 3-2 and 3-3 below.
If the motor temperature protection of the drive is used as an overload protection, the cable
shall be chosen accordingly. If three or more cables are used in parallel for bigger units, each
cable requires a separate overload protection.
These instructions apply only to installations with one motor and one cable connection from
the inverter to the motor. In any other case, ask the factory for more information.
Table 3-1: Cable Types Required to Meet Standards
Fuses, 465 – 800V DC Inverters
Table 3-2: Fuses Used in 465 – 800V DC Inverters
Cable Type EMC Level T
Supply Cable Power cable intended for fixed installation and the specific DC voltage.
Shielded cable not required.
Motor Cable Power cable equipped with concentric protection wire and intended for the
specific mains voltage.
Control Cable Screened cable equipped with compact low-impedance shield.
Nominal
Current Frame
Bussman aR
Fuse Type Fuse Size Fuse U
n
(V) Fuse I
n
(A) No. of Fuses
140 FI9 170M3819 DIN1 690 400 2
170 FI9 170M3819 DIN1 690 400 2
205 FI9 170M6812 DIN3 690 800 2
245 FI9 170M6812 DIN3 690 800 2
300 FI10 170M8547 3SHT 690 1250 2
385 FI10 170M8547 3SHT 690 1250 2
460 FI10 170M8547 3SHT 690 1250 2
520 FI12 170M8547 3SHT 690 1250 4
590 FI12 170M8547 3SHT 690 1250 4
650 FI12 170M8547 3SHT 690 1250 4
730 FI12 170M8547 3SHT 690 1250 4
820 FI12 170M8547 3SHT 690 1250 4
920 FI12 170M8547 3SHT 690 1250 4
1030 FI13 170M8547 3SHT 690 1250 6
1150 FI13 170M8547 3SHT 690 1250 6
1300 FI13 170M8547 3SHT 690 1250 6
1600 FI14 170M8547 3SHT 690 1250 2 x 6
1940 FI14 170M8547 3SHT 690 1250 2 x 6
2300 FI14 170M8547 3SHT 690 1250 2 x 6