Hitachi hitachi series inverter Welding System User Manual


 
36
Using Intelligent Output Terminals
Run Signal
When the [RUN] signal is selected as an
intelligent output terminal, the inverter outputs
a signal on that terminal when it is in Run
Mode. The output logic is active low, and is
the open collector type (switch to ground).
Option
Code
Terminal
Symbol
Function Name State Description
ON when inverter is in Run Mode
00
RUN Run Signal
OFF when inverter is in Stop Mode
Valid for inputs:
11, 12, AL0 – AL2
Required settings
(none)
Notes:
The inverter outputs the [RUN] signal whenever
the inverter output exceeds the start frequency
specified by parameter B082. The start frequency
is the initial inverter output frequency when it turns
ON.
The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
Example for terminal [11] (default output
configuration shown see page 66):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration see page 66):
See I/O specs on page 21,22.
RY
Inverter output
terminal circuit
CM2 11
RUN
AL1
Power
supply
Load
AL0 AL2
Inverter logic
circuit board
RUN
[FW,RV]
1
0
Output
frequency
t
Run
signal
start freq.
B082
ON