47
“d” Function
Func.
Code
Name Description
Run
Mode
Edit
Units
D006
Intelligent output
terminal status
Displays the state of the intelligent
output terminals:
− −
D007
Scaled output frequency
monitor
Displays the output frequency scaled
by the constant in B086.
Decimal point indicates range:
0 to 3999
−
Hz times
constant
d008
Actual frequency monitor Displays the actual frequency, range
is -400 to 400 Hz
−
Hz
d009
Torque command monitor Displays the torque command, range
is -200 to 200 %
−
%
d010
Torque bias monitor Displays the torque bias value, range
is -200 to 200 %
−
%
d012
Output torque monitor Displays the output torque, range is
-200 to 200 %
−
%
D013
Output voltage monitor Voltage of output to motor,
Range is 0.0 to 600.0V
−
V
d014
Input power monitor Displays the input power, range is 0
to 999.9 kW
−
KW
d015
Watt-hour monitor Displays watt-hour of the inverter,
range is 0 to 9999000
−
D016
Elapsed RUN time monitor Displays total time the inverter has
been in RUN mode in hours.
Range is 0 to 9999 / 1000 to 9999 /
⎡100 to ⎡999 (10,000 to 99,900)
−
hours
D017
Elapsed power-on time
monitor
Displays total time the inverter has
been powered up in hours.
Range is 0 to 9999 / 1000 to 9999 /
⎡100 to ⎡999 (10,000 to 99,900)
−
hours
D018
Heat sink temperature monitor Temperature of the cooling fin, range
is -20~150
− °C
d022
Life check monitor Displays the state of lifetime of
electrolytic capacitors on the PWB
and cooling fan.
− −
d023
Program counter monitor
[EzSQ]
Range is 0 to 1024
− −
d024
Program number monitor
[EzSQ]
Range is 0 to 9999
− −
d025
User monitor 0
[EzSQ]
Result of EzSQ execution, range is
–2147483647~2147483647
− −
d026
User monitor 1
[EzSQ]
Result of EzSQ execution, range is
–2147483647~2147483647
− −
d027
User monitor 2
[EzSQ]
Result of EzSQ execution, range is
–2147483647~2147483647
− −
Lifetime expired
Normal
Electrolytic caps
Cooling fan
ON
OFF
Relay
12 11