Fuse Sizes
Distribution fuse size marking is included in the manual to indicate that the unit shall be
connected with a Listed Cartridge Nonrenewable fuse, rated 600 Vac with the current ratings as
shown in the table below or Type E Combination Motor Controller marking is included in the
manual to indicate that the unit shall be connected with,LS Industrial System Co.,Ltd,Type E
Combination Motor Controller MMS Series with the ratings as shown in the table below:
Inverter Model Type Fuse Rating Type E CMC
WJ200-001S
WJ200-002S
WJ200-004S
10A, AIC 200kA
WJ200-007S 20A, AIC 200kA
WJ200-015S
WJ200-022S
30A, AIC 200kA
MMS-32H,240V,40A
WJ200-001L
WJ200-002L
WJ200-004L
10A, AIC 200kA
WJ200-007L
WJ200-015L
15A, AIC 200kA
WJ200-022L 20A, AIC 200kA
WJ200-037L 30A, AIC 200kA
MMS-32H,240V,40A
WJ200-055L
WJ200-075L
60A, AIC 200kA
WJ200-110L
WJ200-150L
80A, AIC 200kA
MMS-100H,240V,80A
WJ200-004H
WJ200-007H
WJ200-015H
WJ200-022H
10A, AIC 200kA
WJ200-030H
WJ200-040H
15A, AIC 200kA
WJ200-055H
WJ200-075H
30A, AIC 200kA
WJ200-110H
WJ200-150H
Class J
50A, AIC 200kA
MMS-32H,480V,40A
or
MMS-63H,480V,52A