Motor Constants Functions
“H” Function Defaults
Func.
Code
Name Description
Run
Mode
Edit
Initial data Units
H001
Auto-tuning selection Three option codes:
00Disabled
01Enabled with motor stop
02Enabled with motor rotation
U
00 -
H002
Motor constant selection
U
00 -
H202
Motor constant selection,
2
nd
motor
Two option codes:
00Hitachi standard motor
02Auto tuned data
U
00 -
H003
Motor capacity
U
kW
H203
Motor capacity,
2
nd
motor
Twelve selections:
0.1/0.2/0.4/0.75/1.5/2.2/3.7/
5.5/7.5/11/15/18.5
U
Specified by
the capacity of
each inverter
model
kW
H004
Motor poles setting
U
4 poles
H204
Motor poles setting,
2
nd
motor
Five selections:
2 / 4 / 6 / 8 / 10
U
4 poles
H005
Motor speed response
constant
100. -
H205
Motor speed response
constant, 2
nd
motor
Set range is 1 to 1000
100. -
H006
Motor stabilization constant
100.
H206
Motor stabilization
constant, 2
nd
motor
Motor constant (factory set),
range is 0 to 255
100.
H020
Motor constant R1
(Hitachi motor)
U
Ohm
H220
Motor constant R1,
2
nd
motor (Hitachi motor)
0.001~65.535 ohms
U
Ohm
H021
Motor constant R2
(Hitachi motor)
U
Ohm
H221
Motor constant R2,
2
nd
motor
(Hitachi motor)
0.001~65.535 ohms
U
Ohm
H022
Motor constant L
(Hitachi motor)
U
mH
H222
Motor constant L,
2
nd
motor
(Hitachi motor)
0.01~655.35mH
U
mH
H023
Motor constant I0
(Hitachi motor)
U
A
H223
Motor constant I0,
2
nd
motor
(Hitachi motor)
0.01~655.35A
U
A
H024
Motor constant J
(Hitachi motor)
U
kgm
2
H224
Motor constant J,
2
nd
motor
(Hitachi motor)
0.001~9999 kgm
2
U
Specified by
the capacity of
each inverter
mode
kgm
2
H030
Motor constant R1
(Auto tuned data)
U
ohm
H230
Motor constant R1,
2
nd
motor
(Auto tuned data)
0.001~65.535 ohms
U
ohm
H031
Motor constant R2
(Auto tuned data)
0.001~65.535 ohms
U
Specified by
the capacity of
each inverter
mode
ohm