73
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name Description
ON Clears the UP/DWN frequency memory by forcing it to
equal the set frequency parameter F001. Setting C101
must be set=00 to enable this function to work
29
UDC Remote Control Data
Clearing
OFF UP/DWN frequency memory is not changed
ON
Forces the source of the output frequency setting A001
and the source of the Run command A002 to be from
the digital operator
31
OPE Operator Control
OFF
Source of output frequency set by A001 and source of
Run command set by A002 is used
ON Bit encoded speed select, Bit 1, logical 1
32
SF1 Multi-speed Select,
Bit operation Bit 1
OFF Bit encoded speed select, Bit 1, logical 0
ON Bit encoded speed select, Bit 2, logical 1
33
SF2 Multi-speed Select,
Bit operation Bit 2
OFF Bit encoded speed select, Bit 2, logical 0
ON Bit encoded speed select, Bit 3, logical 1
34
SF3 Multi-speed Select,
Bit operation Bit 3
OFF Bit encoded speed select, Bit 3, logical 0
ON Bit encoded speed select, Bit 4, logical 1
35
SF4 Multi-speed Select,
Bit operation Bit 4
OFF Bit encoded speed select, Bit 4, logical 0
ON Bit encoded speed select, Bit 5, logical 1
36
SF5 Multi-speed Select,
Bit operation Bit 5
OFF Bit encoded speed select, Bit 5, logical 0
ON Bit encoded speed select, Bit 6, logical 1
37
SF6 Multi-speed Select,
Bit operation Bit 6
OFF Bit encoded speed select, Bit 6, logical 0
ON Bit encoded speed select, Bit 7, logical 1
38
SF7 Multi-speed Select,
Bit operation Bit 7
OFF Bit encoded speed select, Bit 7, logical 0
ON Perform overload restriction
39
OLR Overload Restriction
Source Changeover
OFF Normal operation
ON
Setting of b040 is enabled
40
TL Torque Limit Selection
OFF Max. torque is limited with 200%
ON
41
TRQ1 Torque limit switch 1
OFF
ON
42
TRQ2 Torque limit switch 2
OFF
Torque limit related parameters of Powering/regen, and
FW/RV modes are selected by the combinations of
these inputs.
ON
Brake wait time (b124) is valid
44
BOK Brake confirmation
OFF
Brake wait time (b124) is not valid
ON Set ramp times are ignored. Inverter output
immediately follows the freq. command.
46
LAC LAD cancellation
OFF Accel. and/or decel. is according to the
set ramp time
ON Clear the position deviation data
47
PCLR Pulse counter clear
OFF Maintain the position deviation data
ON
Adds the A145 (add frequency) value
to the output frequency
50
ADD ADD frequency enable
OFF
Does not add the A145 value to the
output frequency
ON Force inverter to use input terminals
for output frequency and Run command sources
51
F-TM Force Terminal Mode
OFF
Source of output frequency set by A001 and source of
Run command set by A002 is used
ON Torque control command input is enabled
52
ATR Enable torque
command input
OFF Torque control command input is disabled
ON Clear watt-hour data
53
KHC Clear watt-hour data
OFF No action
ON General purpose input (1) is made ON under EzSQ
56
MI1 General purpose input
(1)
OFF General purpose input (1) is made OFF under EzSQ
ON General purpose input (2) is made ON under EzSQ
57
MI2 General purpose input
(2)
OFF General purpose input (2) is made OFF under EzSQ