Hitachi hitachi series inverter Welding System User Manual


 
56
“A” Function Defaults
Func.
Code
Name Description
Run
Mode
Edit
Initial data Units
a131
Acceleration curve constant Range is 01 to 10.
U
02
a132
Deceleration curve constant Range is 01 to 10.
U
02
A141
A input select for calculate
function
Seven options:
00Operator
01VR
02Terminal [O] input
03Terminal [OI] input
04RS485
05Option
07Pulse train input
U
02
A142
B input select for calculate
function
Seven options:
00Operator
01VR
02Terminal [O] input
03Terminal [OI] input
04RS485
05Option
07Pulse train input
U
03
A143
Calculation symbol Calculates a value based on the
A input source (A141 selects) and
B input source (A142 selects).
Three options:
00ADD (A input + B input)
01SUB (A input - B input)
02MUL (A input * B input)
U
00
A145
ADD frequency An offset value that is applied to
the output frequency when the
[ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
0.00 Hz
A146
ADD direction select Two options:
00Plus (adds A145 value to the
output frequency setting)
01Minus (subtracts A145 value
from the output frequency
setting)
U
00
a150
Curvature of EL-S-curve at the
start of acceleration
Range is 0 to 50%
U
10. %
a151
Curvature of EL-S-curve at the
end of acceleration
Range is 0 to 50%
U
10. %
a152
Curvature of EL-S-curve at the
start of deceleration
Range is 0 to 50%
U
10. %
a153
Curvature of EL-S-curve at the
end of deceleration
Range is 0 to 50%
U
10. %
a154
Deceleration hold frequency Sets the frequency to hold
deceleration, range is 0.0 to
400.0Hz
U
0.0 Hz
a155
Deceleration hold time Sets the duration of deceleration
hold, range is 0.0 to 60.0
seconds
U
0.0 sec.