Hitachi hitachi series inverter Welding System User Manual


 
63
“b” Function Defaults
Func.
Code
Name Description
Run
Mode
Edit
Initial data Units
B087
STOP key enable Select whether the STOP key on the
keypad is enabled, three option
codes:
00Enabled
01Disabled always
02 Disabled for stop
U
00
B088
Restart mode after FRS Selects how the inverter resumes
operation when free-run stop (FRS)
is cancelled, three options:
00Restart from 0Hz
01Restart from frequency
detected from real speed of
motor (freq. matching)
02Restart from frequency
detected from real speed of
motor (active freq. matching)
U
00
b089
Automatic carrier frequency
reduction
Three option codes:
00Disabled
01Enabled, depending on the
output current
02Enabled, depending on the
heat-sink temperature
U
01 -
b090
Dynamic braking usage ratio Selects the rate of use (in %) of the
regenerative braking resistor per
100 sec. intervals, range is 0.0 to
100%.
0%: Function disabled
>0%: Enabled, per value
U
0.0 %
B091
Stop mode selection Select how the inverter stops the
motor, two option codes:
00DEC (decelerate to stop)
01FRS (free-run to stop)
U
00
B092
Cooling fan control Selects when the fan is ON during
inverter operation, three options:
00Fan is always ON
01Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
02Fan is temperature controlled
U
01 -
B093
Clear elapsed time of cooling
fan
Two option codes:
00Count
01Clear
U
00 -
b094
Initialization target data Select initialized parameters, four
option codes:
00All parameters
01All parameters except in/output
terminals and communication.
02Only registered parameters in
Uxxx.
03All parameters except
registered parameters in Uxxx
and b037.
U
00 -
b095
Dynamic braking control
(BRD) selection
Three option codes:
00Disable
01Enable during run only
02Enable always
U
01 -