RuggedCom RS400 Welder User Manual


 
Appendix B – SNMP Trap Summary
RS400 261 ROS™ v3.5
Appendix B – SNMP Trap Summary
The switch generates the standard traps summarized in the following table.
from IF-MIB: linkDown, linkUp
from SNMPv2-MIB: authenticationFailure coldStart
from BRIDGE-MIB: newRoot, topologyChage
from RMON-MIB: risingAlarm, fallingAlarm
from LLDP-MIB: lldpRemoteTablesChange
The switch also generates the proprietary traps which are summarized in this document with
their severity levels. These traps are described in the RC-TRAPS-MIB.
genericTrap,
powerSupplyTrap,
swUpgradeTrap,
cfgChangeTrap
Generic Traps carry information about event in severity and description objects. They are sent
at a time when alarm is generated for device. Here are some examples when RuggedCom
Generic Traps are generated:
heap error (alert)
NTP server failure (notification)
real time clock failure (error)
failed password (warning)
MAC address not learned by switch fabric (error)
BootP client: TFTP transfer failure (error)
received looped back BPDU (error)
received two consecutive confusing BPDUs on port, forcing down (error)
GVRP failed to learn – too many VLANs (warning)