RuggedCom RS400 Welder User Manual


 
Serial Protocols
ROS™ v3.5 76 RS400
Default: 1
The port number as seen on the front plate silkscreen of the switch.
Response Timer
Synopsis: 50 to 10000
Default: 1000 ms
The maximum allowable time to wait for the RTU to start to respond.
Auxiliary TCP Port
Synopsis: 1024 to 65535 or { Disabled }
Default: Disabled
TCP Modbus Server always listens on TCP port 502. It may be additionally configured to listen
on this auxiliary port number, accepting calls on both.
Send Exceptions
Synopsis: { Disabled, Enabled }
Default: Enabled
This parameter enables/disables sending TCP Modbus exception back to the master if
response has not been received from the RTU within expected time.
Link Stats
Synopsis: { Disabled, Enabled }
Default: Enabled
Enables links statistics collection for protocol.
2.3.5 Modbus Client
Figure 47: Modbus Client Form
IP Port
Synopsis: 1 to 65535
Default: 502
A remote port number to which protocol sends TCP connection requests.