Dukane 9001:2000 Welder User Manual


 
126
Dukane Manual Part No. 40356601
DPC
II Plus and EZ Welder System Users Manual
Generator
The generator will not produce an output signal
when triggered if it is OFF LINE. Make sure that
the green power indicator [A] is lit. The status dis-
play should indicate ON LINE which is marked
as [B] in Figure 122. If the generator is OFF
LINE, press the ON LINE control key [C].
Operate Input
If you are using a hand probe, make sure the con-
trol cable is connected to the System Input con-
nector. The trigger on the hand probe activates the
Ultrasonic output through the control cable.
If you have supplied custom automation signals,
pin 8, or pins 3 & 4 of the Operate Input must be
used to trigger the Ultrasonic output. The system
control inputs are user configurable. Refer to Sec-
tion 5, Jumper Block SH707 for a detailed descrip-
tion of the options. The factory default setting
(JU724) is a contact closure to ground. If you are
using the isolated source jumper position (JU 726),
then the input requires a minimum of 5V to trig-
ger the generator.
STATUS
FAULT
ON LINE
INPUT TEST
OVERTEMP
OVERLOAD
OFF LINE
ON
LINE
TEST
OFF
LINE
0
20 40 60
80 100
PERCENTAGE OF AVAILABLE POWER
PERCENTAGE OF AVAILABLE POWER
SYSTEM POWER OUTPUT
Ạạ
Figure 122 Generator ON LINE Key and Indicator
NOTE
Figure 53 shows the male cable end of the
System Input connector and is repeated here.
The cable end connector is a mirror image of
the female panel connector shown in Figure
52. Make sure you have correctly wired the
connector if you are using custom automa-
tion signals.
1 2 3 4 5
6
10
11 12 13 14 15