Emerson 20/20 Air Compressor User Manual


 
3 – 4
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
High Level Shutdown Input:
• This input must be energized in order for the com-
pressor to operate. If de-energized, the compressor
will shut down and issue a high level trip.
Oil Level Float Switch #1 Input:
Used for Cool Compression.
Oil Level Float Switch #2 Input:
Used for Cool Compression.
Remote Select #1/#2 Input:
• This input enables or disables remote I/O control.
Energizing this input enables the Remote Capacity
Increase and Remote Capacity Decrease inputs.
Remote Start/Stop Input:
If the compressor is enabled for remote I/O control,
this input is enabled. Energizing this input will issue
a start for the compressor as long as it is available to
run. De-energizing this input stops the compressor.
Remote Capacity Increase Input:
NOTE
The scan interval on the remote increase and
decrease inputs is approximately ONE SECOND.
Please take that into account when developing
a control scheme using the remote increase and
remote decrease inputs for compressor control.
If the compressor is enabled for remote I/O control,
this input is enabled. Operational only when the com-
pressor is running. Energizing this input will increase
the slide valve position.
The slide valve will continuously increase as long as
this input is energized. The slide valve will not in-
crease when this input is de-energized.
Remote Capacity Decrease Input:
• Operational only when the compressor is running.
This input is enabled if the compressor is enabled
for remote I/O control. Energizing this input will de-
crease the slide valve position. The slide valve will
continuously decrease as long as this input is ener-
gized. The slide valve will not decrease when this in-
put is de-energized.
Condenser Step #1 Output:
• This output is enabled when condenser control op-
tion is selected. A condenser fan or pump will be
turned on or off by this output.
Condenser Step #2 Output:
• This output is enabled when condenser control op-
tion is selected. A condenser fan or pump will be
turned on or off by this output.
Condenser Step #3 Output:
• This output is enabled when condenser control op-
tion is selected. A condenser fan or pump will be
turned on or off by this output.
Condenser Step #4 Output:
• This output is enabled when condenser control op-
tion is selected. A condenser fan or pump will be
turned on or off by this output.
Auxiliary Inputs #1 - #8:
• Optional inputs that can be con gured as an alarm
or trip. Typically connected to external switched
devices.
Auxiliary Outputs #1 - #4:
• Optional inputs that can be con gured as an alarm
or trip. Typically connected to external switched
devices.
Analog Inputs
Refer to Table 2-2. Analog Inputs.
Motor Current:
Default is a 0-5 Amp current transformer (CT). Current
transformer ratio is set in the calibration screen.
Suction Pressure:
• Default signal is 4-20mA. Suction pressure trans-
ducer range and calibration is set in the calibration
screen.
Discharge Pressure
• Default signal is 4-20mA. Discharge pressure trans-
ducer range and calibration is set in the calibration
screen.
Oil Filter Inlet Pressure:
• Default signal is 4-20mA. Oil lter pressure trans-
ducer range and calibration is set in the calibration
screen.
Oil Manifold Pressure:
Default signal is 4-20mA. Oil manifold pressure trans-
ducer range and calibration is set in the calibration
screen.
Economizer Pressure:
Default signal is 4-20mA. Economizer pressure trans-
ducer range and calibration is set in the calibration
screen.
Slide Valve Position:
Reads the 0-5 volt signal back from the slide posi-
tion motor actuator to indicate current slide valve
position.
Section 3 • Hardware Architecture