Emerson 20/20 Air Compressor User Manual


 
3 – 13
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
CHANNEL 5 SIGNAL JP-13 JP-14 JP-15 JP-31
Analog Input 5 0-5 VOLT OUT OUT OUT OUT
1-5 VOL
T OUT OUT OUT OUT
0-10 VOLT OUT OUT IN OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
RTD OUT OUT OUT IN
Table 3-4. Analog Input Jumper Tables (Continued)
CHANNEL 6 SIGNAL JP-16 JP-17 JP-18 JP-32
Analog Input 6 0-5 VOLT OUT OUT OUT OUT
1-5 VOLT OUT OUT OUT OUT
0-10 VOLT OUT OUT IN OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
RTD OUT OUT OUT IN
CHANNEL 7 SIGNAL JP-19 JP-20 JP-21 JP-33 JP-25
Analog Input 7 0-5 VOLT OUT OUT OUT OUT 2
1-5 VOL
T OUT OUT OUT OUT 2
0-10 VOLT OUT OUT IN OUT 2
4-20 mA IN OUT OUT OUT 2
ICTD OUT IN OUT OUT 2
RTD OUT OUT OUT IN 2
ACTUATOR OUT OUT OUT OUT 1
POTENTIOMETER OUT OUT OUT OUT 3
CHANNEL 8 SIGNAL JP-22 JP-23 JP-24 JP-34 JP-26
Analog Input 8 0-5 VOLT OUT OUT OUT OUT 2
1-5 VOL
T OUT OUT OUT OUT 2
0-10 VOLT OUT OUT IN OUT 2
4-20 mA IN OUT OUT OUT 2
ICTD OUT IN OUT OUT 2
RTD OUT OUT OUT IN 2
ACTUATOR OUT OUT OUT OUT 1
POTENTIOMETER OUT OUT OUT OUT 3
Section 3 • Hardware Architecture