Emerson 20/20 Air Compressor User Manual


 
3 – 12
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
Section 3 • Hardware Architecture
Analog Input Jumper Tables
The following tables are used to con gure each channel of the analog input board signal type and range desired by the
operator, see Table 2-4. Analog Input Jumper Tables.
CHANNEL 1 SIGNAL JP-1 JP-2 JP-3 JP-27 JP-35
Analog Input 1-A* 0-5 AMP OUT OUT OUT OUT IN
Analog input 1-B** 0-5 VOLT OUT OUT OUT OUT OUT
1-5 VOLT OUT OUT OUT OUT OUT
0-10 VOLT OUT OUT IN OUT OUT
4-20 mA IN OUT OUT OUT OUT
ICTD OUT IN OUT OUT OUT
RTD OUT OUT OUT IN OUT
*Use Analog Input 1-A when 0-5 AMP secondary current transformers are installed in the motor starter.
**Use Analog Input 1-B when current transformers are installed in the motor starter.
CHANNEL 2 SIGNAL JP-4 JP-5 JP-6 JP-28
Analog Input 2 0-5 VOLT OUT OUT OUT OUT
1-5 VOL
T OUT OUT OUT OUT
0-10 VOLT OUT OUT IN OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
RTD OUT OUT OUT IN
CHANNEL 3 SIGNAL JP-7 JP-8 JP-9 JP-29
Analog Input 3 0-5 VOLT OUT OUT OUT OUT
1-5 VOL
T OUT OUT OUT OUT
0-10 VOLT OUT OUT IN OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
RTD OUT OUT OUT IN
Table 3-4. Analog Input Jumper Tables
CHANNEL 4 SIGNAL JP-10 JP-11 JP-12 JP-30
Analog Input 4 0-5 VOLT OUT OUT OUT OUT
1-5 VOLT OUT OUT OUT OUT
0-10 VOLT OUT OUT IN OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
RTD OUT OUT OUT IN