Emerson 20/20 Air Compressor User Manual


 
9 – 1
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
Section 9 Compressor Scheduling
Overview
This menu allows the operator to schedule control set-
point switching during the day and week. This feature
can be enabled and disabled from the Compressor
Schedule screen. Up to four setpoint “switch” events
can be scheduled per day, see Figure 9-1. Compressor
Scheduling Screen.
Scheduling Setpoint
Schedule:
The options for selection are “Enable” & “Disable”.
The operator is allowed to con gure setpoints relat-
ed to schedule events, but only when the schedule is
disabled.
• The operator can Enable Compressor Scheduling
Feature, only if Time Intervals are in order of Event 1
< Event 2 < Event 3 < Event 4 for all days. If events are
not in order, invalid events are marked with caution
symbol to indicate the operator to correct events and
then enable feature.
Control Mode:
• These drop-down boxes allow selection of operat-
ing modes which gets switched once schedule event
time is achieved.
The list of allowable modes depends on the number
of controllers selected in the con guration screen.
For example, if the number of Suction Pressure
Control Setpoints selected is “2” and the number
of Process Temperature Control Setpoints selected
is “1”, then Control Mode drop-down box will have
“Unscheduled”, “Suction Pressure SP1”, “Suction
Pressure SP2” and “Process Temperature SP1” as op-
tions for selection.
• If Control Mode is selected as “Unscheduled” and
Time set in an event is achieved, then control mode
will not get switched. Hence Control Mode can be set
Figure 9-1. Compressor Scheduling Screen