Lincoln Electric SVM150-A Welder User Manual


 
TABLE A.1 – TOTAL COMBINED LENGTH
OF ELECTRODE AND WORK CABLES
Cable
Cable Size for
Length
250 Amps
100% Duty Cycle
0-100 ft. (0-30 meters) 1 AWG
100-200 ft. (30-46 meters) 1 AWG
150-200 ft. (46-61 meters) 1/0 AWG
CABLE INSTALLATION
Install the welding cables to your Ranger 250 as fol-
lows.
1. The engine must be OFF to install welding cables.
2. Remove the flanged nuts from the output terminals.
3. Connect the electrode holder and work cables to
the weld output terminals. The terminals are iden-
tified on the case front.
4. Tighten the flanged nuts securely.
5. Be certain that the metal piece you are welding (the
“work”) is properly connected to the work clamp
and cable.
6. Check and tighten the connections periodically.
• Loose connections will cause the output terminals to
overheat. The terminals may eventually melt.
• Do not cross the welding cables at the output termi-
nal connection. Keep the cables isolated and sepa-
rate from one another.
AUXILIARY POWER RECEPTACLES
The auxiliary power of the Ranger 250 consists of two
20 amp-120 VAC (5-20R) duplex receptacles and one
50 amp 120/240 VAC (14-50R) receptacle. The 240
VAC receptacle can be split for single-phase 120 VAC
operation.
The auxiliary power capacity is 8,000 watts of 60 Hz,
single-phase power. The auxiliary power capacity rat-
ing in watts is equivalent to volt-amperes at unity power
factor. The maximum permissible current of the 240
VAC output is 33 amps. The 240 VAC output can be
split to provide two separate 120 VAC outputs with a
maximum permissible current of 33 amps per output to
two separate 120 VAC branch circuits (these circuits
cannot be paralleled). Output voltage is within ±10% at
all loads up to rated capacity.
The 120 VAC auxiliary power receptacles should only
be used with three-wire grounded type plugs or
approved double insulated tools with two-wire plugs.
The current rating of any plug used with the system
must be at least equal to the current capacity of the
associated receptacle.
NOTE: The 240 VAC receptacle has two 120 VAC cir-
cuits, but they are of opposite polarities and cannot be
paralleled.
STANDBY POWER CONNECTIONS
The Ranger 250 is suitable for temporary, standby or
emergency power using the engine manufacturer’s rec-
ommended maintenance schedule.
The Ranger 250 can be permanently installed as a
standby power unit for 240 VAC, three-wire, single-
phase, 35 amp service. Connections must be made by
a licensed electrician who can determine how the
120/240 VAC power can be adapted to the particular
installation and comply with all applicable electrical
codes. The following information can be used as a
guide by the electrician for most applications. Refer to
the connection diagram in Figure A-2.
1. Install the double-pole, double-throw switch
between the power company meter and the
premises disconnect. Switch rating must be the
same or greater than the customer’s premises dis-
connect and service over current protection.
2. Take necessary steps to assure load is limited to
the capacity of the Ranger 250 by installing a 35
amp, 240 VAC double-pole circuit breaker.
Maximum rated load for each leg of the 240 VAC
auxiliary is 33 amperes. Loading above the rated
output will reduce output voltage below the allow-
able ±10% of rated voltage, which may damage
appliances or other motor-driven equipment and
may result in overheating of the Ranger 250 engine
and/or alternator windings.
3. Install a 50 amp, 120/240 VAC plug (NEMA Type
14-50) to the double-pole circuit breaker using No.
6, 4-conductor cable of the desired length. (The 50
amp, 120/240 VAC plug is available in the optional
K802R plug kit or as part number T12153-9.)
4. Plug this cable into the 50 amp, 120/240 VAC
receptacle on the Ranger 250 case front.
INSTALLATION
A-7 A-7
RANGER 250
Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOC
Return to Master TOC Return to Master TOC Return to Master TOC Return to Master TOC
CAUTION