Low Load Detection Parameters
The following parameters work in
conjunction with the intelligent output
function, when configured. The output
mode parameter (C038) sets the mode of
the detection at which the low load
detection signal [LOC] turns ON. Three
kinds of modes can be selected. The
detection level parameter (C039) is to set
the level of the low load.
This function is for generating an early
warning logic output, without causing
either a trip event or a restriction of the
motor current (those effects are available
on other functions).
“C” Function Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Output mode of low load
detection signal
C038
LOC MODE CRT
Three option codes:
00}Disabled
01}During acceleration, deceleration
and constant speed
02}During constant speed only
U
01 01
Low load detection levelC039
LOC LVL 02.60A
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
U
INV
rated
curr.
INV
rated
curr.
A
C039
Output
current
[LOC]
output
0
1
0
t
t
357
Configuring Drive
Parameters
3 57
&RQ¿JXULQJ'ULYH
Parameters