List of Holding Registers
Network Data
Func.
Code
Name R/W Description
Reg. Range Res.
B052 OV-LAD Stop level of
non stop operation
setting
R/W Setting the OV-LAD stop level of
non stop operation. Range is 0.0
to 1000.0
10CBh 0 to 10000 0.1 V
B053 Deceleration time of
non stop operation
setting
R/W Range is 0.1 to 3000 10CCh 1 to 30000 0.1 sec
B054 Frequency width of
quick deceleration
setting
R/W Setting of the first quick
deceleration width. Range is 0.0
to 10.0
10CEh 0 to 100 0.1 Hz
B055 DC bus AVR P-gain R/W Proportional gain adjustment for
DC bus AVR function. Range is:
0.2 to 5.0
1173h 2 to 50 0.1
B056 DC bus AVR I-time R/W Integration time adjustment for
DC bus AVR function. Range is:
0.0 to 150.0
1174h 0 to 1500 0.1s
B080 [AM]analog signal gain R/W Adjust of analog output at
terminal [AM],
range is 0 to 255
10CFh 0 to 255
B082 Start frequency
adjustment
R/W Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
10D1h 5 to 99 0.1 Hz
B083 Carrier frequency
setting
R/W Sets the PWM carrier (internal
switching frequency), range is
2.0 to 12.0 kHz
10D2h 20 to 120 0.1 Hz
B084 Initialization mode
(parameters or trip
history)
R/W Select the type of initialization to
occur, three option codes:
00}Trip history clear
01}Parameter initialization
02} Trip history clear and
parameter initialization
10D3h 0, 1, 2
B085 Country for
initialization
R/W Select default parameter values
for country on initialization,
three option codes:
00}Japan
01}Europe
02}US
10D4h