Hitachi CONVENTION 14 Welding System User Manual


 
Reset Inverter
The [RS] terminal causes the inverter to execute
the reset operation. If the inverter is in Trip Mode,
the reset cancels the Trip state. When the signal
[RS] is turned ON and OFF, the inverter executes
the reset operation. The minimum pulse width for
[RS] must be 12 ms or greater. The alarm output
will be cleared within 30 ms after the onset of the
Reset command.
W
ARNING: After the Reset command is given and the alarm reset occurs, the motor
will restart suddenly if the Run command is already active. Be sure to set the alarm
reset after verifying that the Run command is OFF to prevent injury to personnel.
Option
Code
Terminal
Symbol
Function Name State Description
ON The motor output is turned OFF, the Trip Mode is
cleared (if it exists), and powerup reset is applied
18 RS Reset Inverter
OFF Normal power ON operation
Valid for inputs: C001~C005
Required settings (none)
Notes:
x While the control terminal [RS] input is ON, the
keypad displays alternating segments. The
SRW optional remote keypad displays
“HELLO!!”. After RS turns OFF, the display
recovers automatically.
x Pressing the Stop/Reset key of the digital
operator can generate a reset operation only
when an alarm occurs.
Example (default input configuration shown—see
page 3–49):
See I/O specs on page 4–6.
x A terminal configured with the [RS] function can only be configured for normally open operation. The
terminal cannot be used in the normally closed contact state.
x When input power is turned ON, the inverter performs the same reset operation as it does when a
pulse on the [RS] terminal occurs.
x The Stop/Reset key on the inverter is only operational for a few seconds after inverter powerup when
a hand-held remote operator is connected to the inverter.
x If the [RS] terminal is turned ON while the motor is running, the motor will be free running
(coasting).
x If you are using the output terminal OFF delay feature (any of C145, C147, C149 > 0.0 sec.), the [RS]
terminal affects the ON-to-OFF transition slightly. Normally (without using OFF delays), the [RS]
input causes the motor output and the logic outputs to turn OFF together, immediately. However,
when any output uses an OFF delay, then after the [RS] input turns ON, that output will remain ON
for an additional 1 sec. period (approximate) before turning OFF.
5 4 3 2 1 L
PCS
P24
RS
- FE models
[RS]
1
0
t
Alarm
signal
1
0
Approx. 30 ms
12 ms
minimum
423
Operations and
Monitoring
4 23
Operations and
Monitoring