Miscellaneous Functions
The following table contains miscellaneous functions not in other function groups.
“C” Function Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Debug mode enable *C091
DBG Slct OFF
Displays debug parameters.
Two option codes:
00}Disable
01}Enable <
Do not set>
(for factory use)
9
00 00
Up/Down memory mode
selection
C101
UP/DWN NO-STR
Controls speed setpoint for the
inverter after power sycle.
Two option codes:
00}Clear last frequency (return to
default frequency F001)
01}Keep last frequency adjusted
by UP/DWN
U
00 00
Reset selectionC102
RS Slct ON
Determines response to Reset
input [RS].
Three option codes:
00}Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01}Cancel trip state at signal
OFF transition, stops inverter
if in Run Mode
02}Cancel trip state at input ON
transition, no effect if in Run
Mode
U
00 00
CAUTION: Do not change Debug mode for safety reasons. Otherwise unexpected
performances may occur.
362
Configuring Drive
Parameters
3 62
&RQ¿JXULQJ'ULYH
Parameters