Hitachi CONVENTION 14 Welding System User Manual


 
List of Holding Registers
Network Data
Func.
Code
Name R/W Description
Reg. Range Res.
A104 [OI]-[L] input active
range end voltage
R/W The ending point (offset) for the
current input range,
range is 0. to 100.%
1084h 0 to 100 1 %
A105 [OI]-[L] input start
frequency enable
R/W Two options; select codes:
00 }Use offset (A101 value)
01 }Use 0Hz
1085h 0, 1
A141 A input select for
calculate function
R/W Five options:
00}Digital operator
01}Keypad potentiometer
02}[O] input
03}[OI] input
04}Network variable
108Eh 0 to 4
A142 B input select for
calculate function
R/W Five options:
00}Digital operator
01}Keypad potentiometer
02}[O] input
03}[OI] input
04}Network variable
108Fh 0 to 4
A143 Calculation symbol R/W Calculates a value based on the
A input source (A141 selects) and
B input source (A142 selects).
Three options:
00}ADD (A input + B input)
01}SUB (A input - B input)
02}MUL (A input * B input)
1090h 0, 1, 2
A145 ADD frequency R/W An offset value that is applied to
the output frequency when the
[ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
1091h 0 to 4000 0.1 Hz
A146 ADD direction select R/W Two options:
00}Plus (adds A145 value to the
output frequency setting)
01}Minus (subtracts A145 value
from the output frequency etting)
1093h 0, 1
A151 POT active range start
frequency
R/W The output frequency
corresponding to the POT range
starting point,
range is 0.0 to 400.0 Hz
1095h 0 to 4000 0.1 Hz
A152 POT input active range
end frequency
R/W The output frequency
corresponding to the POT range
ending point,
range is 0.0 to 400.0 Hz
1097h 0 to 4000 0.1 Hz
A153 POT input active range
start
R/W The starting point (offset) for the
POT range, range is 0. to 100.%
1098h 0 to 100 1 %
A154 POT input active range
end
R/W The ending point (offset) for the
POT range, range is 0. to 100.%
1099h 0 to 100 1 %
A155 POT input start
frequency enable
R/W Two options; select codes:
00}Use offset (A151 value)
01}Use 0Hz
109Ah 0, 1
Note 1: When the value is 10000 (100.0 seconds), a value in the second decimal place
is ignored. (for A092/A292 and A093/A293).
B30
Appendix B
B 30
Appendix B