Wiring – Warnings for Electrical Practice and Wire Specifications
WARNING: “USE 60/75qC Cu wire only” or equivalent. For models X200-005S, -007S,
-011S, -022S, -007N, -015N, -015L, -022L, -037L, -055L, -075L.
WARNING: “USE 75qC Cu wire only” or equivalent. For models X200-002S, -004S, -
002N, -004N, -002L, -004L, -007L, -022H, -030H, -037H, -040H, -055H, -075H.
WARNING: “USE 60qC Cu wire only” or equivalent. For models X200-004H, -007H, and
–015H.
W
ARNING: “Open Type Equipment.”
W
ARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 240V maximum when protected by Class CC, G, J or R fuses or
circuit breaker having an interrupting rating not les than 100,000 rms symmetrical
amperes, 240 volts maximum”. For models with suffix S, N or L.
W
ARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 480V maximum when protected by Class CC, G, J or R fuses or
circuit breaker having an interrupting rating not les than 100,000 rms symmetrical
amperes, 480 volts maximum.” For models with suffix H.
H
IGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a danger of electric
shock and/or fire.
H
IGH VOLTAGE: Wiring work shall be carried out only by qualified personnel.
Otherwise, there is a danger of electric shock and/or fire.
H
IGH VOLTAGE: Implement wiring after checking that the power supply is OFF.
Otherwise, you may incur electric shock and/or fire.
H
IGH VOLTAGE: Do not connect wiring to an inverter operate an inverter that is not
mounted according to the instructions given in this manual.
Otherwise, there is a danger of electric shock and/or injury to personnel.
W
ARNING: Make sure the input power to the inverter is OFF. If the drive has been
powered, leave it OFF for five minutes before continuing.
C
AUTION: Power terminal assignment is different compared to old models such as
L100, L200 series, etc,. Pay attention when wiring the power cable.