Analog Input Operation
The X200 inverters provide for analog input to
command the inverter frequency output value.
The analog input terminal group includes the
[L], [OI], [O], and [H] terminals on the control
connector, which provide for Voltage [O] or
Current [OI] input. All analog input signals
must use the analog ground [L].
If you use either the voltage or current analog
input, you must select one of them using the
logic input terminal function [AT] analog type.
Refer to the table on next page showing the
activation of each analog input by combination
of A005 set parameter and [AT] terminal
condition. The [AT] terminal function is covered
in “Analog Input Current/Voltage Select” on
page 4–22. Remember that you must also set
A001 = 01 to select analog input as the
frequency source.
N
OTE: If no logic input terminal is configured for the [AT] function, then inverter
recognizes that [AT]=OFF.
Using an external potentiometer is a common way
to control the inverter output frequency (and a good
way to learn how to use the analog inputs). The
potentiometer uses the built-in 10V reference [H]
and the analog ground [L] for excitation, and the
voltage input [O] for the signal. By default, the [AT]
terminal selects the voltage input when it is OFF.
Take care to use the proper resistance for the
potentiometer, which is 1~2 k
:, 2 Watts.
V
oltage Input – The voltage input circuit uses
terminals [L] and [O]. Attach the signal cable’s
shield wire only to terminal [L] on the inverter.
Maintain the voltage within specifications (do not
apply negative voltage).
C
urrent Input – The current input circuit uses
terminals [OI] and [L]. The current comes from a
sourcing
type transmitter; a
sinking
type will not
work! This means the current must flow into
terminal [OI], and terminal [L] is the return back
to the transmitter. The input impedance from
[OI] to [L] is 250 Ohms. Attach the cable shield
wire only to terminal [L] on the inverter.
AM H O OI L
+V Ref.
Voltage input
Current input
A
GND
AM H O OI L
Freq.
settin
g
A001
V/I input
select
[AT]
Å
+
-
4-20 mA
0-10 V
AM H O OI L
1 to 2k:, 2W
0 to 9.6 VDC,
0 to 10V nominal
AM H O OI L
+
-
4 to 19.6 mA DC,
4 to 20mA nominal
AM H O OI L
Å
See I/O specs on page 4-6.
455
Inverter Mounting
and installation
4 55
Operations and
Monitoring