Example Wiring Diagram
The schematic diagram below provides a general example of logic connector wiring, in
addition to basic power and motor wiring converted in Chapter 2. The goal of this
chapter is to help you determine the proper connections for the various terminals shown
below for your application needs.
45
Operations and
Monitoring
Breaker,
MCCB or GFI
Power source,
3-phase or 1-
phase, per
inverter model
Input
circuits
24V
P24
L
+ -
1
2
3
4
5
Forward
Reverse
Thermistor
Intelligent inputs,
5 terminals
GND for logic inputs
NOTE: For the wiring
of intelligent I/O and
analog inputs, be sure
to use twisted pair /
shielded cable. Attach
the shielded wire for
each signal to its
respective common
terminal at the inverter
end only.
[5] configurable as
discrete input or
thermistor input
AM
Meter
H
O
OI
L
A
nalog reference
0~10VDC
4~20mA
GND for analog signals
X200
Motor
PD/+1
P/+
R
(L1)
S
(L2)
T
N(L3)
U
(T1)
V
(T2)
W
(T3)
Braking
unit
(optional)
N/-
DC reactor
(optional)
AL1
AL0
AL2
Relay contacts,
type 1 Form C
11
CM2
Load
Freq. arrival signal
Open collector output
Output circuit
GND for logic outputs
PCS
+
-
4 5
Operations and
Monitoring