Configuring Scan Delay [ DYi ]
EDIT
> SETUP > PROG > DELAY
Value: 100
Range: 099,999
Scan Debounce
DELAY (ms):100
Sets the amount of time required for the program select inputs (BCD or Binary) to
remain stable before they are valid. The minimum time is 2 ms. If program select
inputs are not stable for a time equal to or greater than the specified delay, the
program will not be executed. Use the numeric keys to enter a value in ms.
Note: See Data Valid Input Configuration for an alternate approach.
Select value, press ENTER
Configure Serial Communications
To use the LinStep+ serial port, several things must be done first. Use the keypad
to set the autoecho and the units daisy chain address. The baud rate and other
parameters have fixed values and may not be changed.
S Baud rate: 9600
S Data bits: 8
S Stop bits: 1
S Parity: none
Action Display Comments
RS232C SETUP
ECHO UNIT#
Select a submenu, press F1 (ECHO),
F2 (UNIT#).
Configuring Echo Enable [ ECi ]
EDIT
> SETUP > RS232 > ECHO
Value: Enabled
Range: Enabled, Disabled
RS232C ECHO
ENABLED
Enable or disable the RS232C ECHO feature. If ECHO is disabled,
characters received by the controls serial port will not be
retransmitted. ECHO must be enabled in daisychain applications.
Select value, press ENTER
Configuring Unit Number [ UNi ]
EDIT
> SETUP > RS232 > UNIT#
Value: 1
Range: 199
Unit Number
NUMBER:1
Set the units address. Each unit in an RS232C serial daisy chain
of multiple units must have a unique Unit Number.
Select value, press ENTER