6Safety
6.4.3 EMC measures
There are mainly following items in the EMC measures.
(1) Store into the sealed metal board.
(2) Grounding all the conductor that have floated electrically (makes the impedance low).
(3) Wiring so that the power source wire and signal wire are separated.
(4) Use the shield cable for the cable which wired outside of the metal board.
(5) Install the noise filter.
To suppress the noise emitted out of the board, be careful of the following item.
(1) Ensure grounding of the equipment.
(2) Use the shield cable.
(3) Separate the metal board electrically. Narrows the distance/hole.
The strength of electromagnetic noise emitted to environment is changed a lot by the shielding efficiency
of cable and the distance of metal board, so it should be careful.
6.4.4 Component parts for EMC measures
(1) Ferrite core
The ferrite core is mounted by the plastics case as one. It can attach by the one-touch, without cutting the cable.
This has the effect in the common-mode noise. The measures against the noise are made not influential in the
quality of the signal.
There are the following as an example.
(2) Line noise filter
Type FR-BLF (Mitsubishi Electric Corp.)
Maker: SEIWA ELECTRIC MFG. Co.,Ltd.
Type
Outside dimension (mm) Diameter of the
adaptation cable
[max] (mm)
ABCD
E04SR401938 61 38 19 40 19.0
E04SR301334 39 34 13 30 13.0
Maker: TAKACHI ELECTRONICS ENCLOSURE CO., LTD.
Type
Outside dimension (mm) Diameter of the
adaptation cable
[max] (mm)
ABCD
TFT-274015S 43.8 27.4 20.7 - φ26.5