Toshiba VF-AS1 Welding System User Manual


 
E6581301
F-68
6
6.33.24
Protection against a failure of the control power backup device (optional CPS002Z)

H
HH
H : Control power supply backup option failure monitoring
• Function
If the control power backup device (optional CPS002Z) fails to supply power for some reason or other for fifteen
minutes and over, the inverter will put out an alarm signal or a trip signal depending on the setting.
Leaving this parameter disabled may cause the main power supply to be turned on and off endlessly if
something unusual occurs, depending on your sequence etc., so you should set this parameter
H
properly
when using the optional power backup device.
Title Function Adjustment range Default setting
H
Control power supply backup
option failure monitoring
: Control power supply not backed up
: Control power supply backed up
(alarm in the event of a failure)
: Control power supply backed up
(tripping in the event of a failure)

H
=
: If control power is not backed up with an external backup device:
Select this setting if an external backup device is not connected to the inverter’s control terminals +SU and CC.
Note: Even if
H
is set to
while control power is backed up, the inverter will cut off the power supply and
issue
EQHH
alarm in the event the backup device fails during operation.
If the backup device is already faulty when it is turned on, it will not be recognized to be faulty even if this
setting is selected.
H
=
: If control power is backed up with an external backup device (alarm signal output):
If
H
is set to
, however, the inverter will cut off the power supply, let the motor coast, and raise a
EQHH
alarm in the event something unusual (voltage drop) occurs with the power supplied through the +SU and CC
terminals.
Once the
EQHH
alarm has been raised, the inverter is not reset even if the control voltage returns to its normal
level. To reset the inverter, turn off the main circuit power supply.
H
=
: If control power is backed up with an external backup device (trip signal output):
This setting trips the inverter in the event something unusual (voltage drop) occurs with the external control power
backup device. Trip code
G
is displayed.
In the event of this trip, unlike ordinary trips, the inverter is held tripped regardless of the setting of
H
(inverter trip retention selection).
This setting is effective only when the inverter is used in a standard connection shown in Chapter 2.
If reset the trip, operate with
H
=
or
setting.
Note: Be sure to set the parameter
H
to 1 if the main power supply is turned on and off endlessly for reasons of
sequence, as shown below, in the event the control power backup device fails.
For details, refer to section 6.33.2.
R/L1
S/L2
T/L3
+SU
CC
FLA
FLB
FLC
MC
RUN
Control power supply
backup option (CPS002Z)
In case of
3
φ
- 200~240V
-50/60Hz
MC
RUN
6.33.25
Ground fault detection selection
H
HH
H : Ground fault detection selection
• Function
If the trip EF2 occurred because the DC input terminals (PA, PC) of inverter is connected to a power source,
Set
H
=1.
Title Function Adjustment range Default setting
H

Ground fault detection selection
: Detection (except in stop)
: No detection

Note) This function is only effective for 200V-15kW or less and 400V-18.5kW and 600V-7.5kW or less.