Toshiba VF-AS1 Welding System User Manual


 
E6581301
E-13
5
4) Vector control–increasing starting torque and achieving high-precision
operation.
Setting of V/f control mode selection RV
RVRV
RV=
,
(Sensorless vector control 1, 2)
Using sensorless vector control with a Toshiba standard motor will provide the highest torque at the lowest speed
ranges. The effects obtained through the use of sensorless vector control are described below.
(1) Provides large starting torque.
(2) Effective when stable operation is required to move smoothly up from the lowest speeds.
(3) Effective in elimination of load fluctuations caused by motor slippage.
(4) Effective in producing high motor torque at low speed.
Set RV to (sensorless vector control 1) to operate multiple motors of the same type in parallel or to operate a
motor with a two or more notches lower rating.
To perform torque control, set RV to (sensorless vector control 2), which is designed to perform operation control
with higher accuracy. In that case, however, the inverter should be used only for operating a single motor with an
equal or one notch lower rating.
Ŭ
Motor constant must be set.
The motor constant can be set in any of the following two ways:
1) Automatic setting
Enter the following information that is indicated on the motor nameplate, and then execute the auto-tuning 1
command (Set H to , and then reset H to .).
<Information indicated on motor nameplate>
XN (Base frequency), XNX (Base frequency voltage), H (Motor rated capacity), H (Motor rated
current), H(Motor rated rotational speed)
Refer to 6.22 selection 2.
2) Manual setting
Set each motor constant manually.
Refer to 6.22 selection 3.
5) Setting of V/f characteristic arbitrarily
Setting of V/f control mode selection RV
RVRV
RV=
(V/f 5-point setting)
In this mode, the base frequency and the base frequency voltage for the V/f control need to be set to operate the
motor while switching a maximum of 5 different V/f characteristics.
[Parameter setting]
Title Function Adjustment range Default setting
H V/f 5-point setting VF1 frequency ~HJ Hz 
H V/f 5-point setting VF1 voltage ~ % * 
H V/f 5-point setting VF2 frequency ~HJ Hz 
H V/f 5-point setting VF2 voltage ~ % * 
H V/f 5-point setting VF3 frequency ~HJ Hz 
H V/f 5-point setting VF3 voltage ~ % * 
H V/f 5-point setting VF4 frequency ~HJ Hz 
H V/f 5-point setting VF4 voltage ~ % * 
H V/f 5-point setting VF5 frequency ~HJ Hz 
H V/f 5-point setting VF5 voltage ~ % * 
*100% adjustment value (200V class: 200V, 400V class: 400V)