Toshiba VF-AS1 Welding System User Manual


 
E6581301
11
K-14
[14] Functions for lift [2/2] Sensorless vector/vector with sensor (Ɣ:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
Speed
control
Torque
control
H
0348 Braking time learning function
0:Disabled
1:Brake signal learning (0 after adjustment)
1/1 0 Enabled Ɣ/Ɣ - - - 6. 17
H
0349
Acceleration/deceleration
suspend function
0:Disabled, 1:Parameter setting, 2:Terminal input 1/1 0 Disabled Ɣ/Ɣ - Ɣ Ɣ 6. 18
H
0350
Acceleration suspend frequency
0.0~
HJ
Hz
0.1/0.01
0.0
Enabled
Ɣ/Ɣ
-
Ɣ
Ɣ
6. 18
H
0351
Acceleration suspend time
0.0~10.0 sec.
0.1/0.1
0.0
Enabled
Ɣ/Ɣ
-
Ɣ
Ɣ
6. 18
H
0352
Deceleration suspend
frequency
0.0~HJ Hz 0.1/0.01 0.0 Enabled Ɣ/Ɣ - Ɣ Ɣ 6. 18
H
0353
Deceleration suspend time
0.0~10.0 sec.
0.1/0.1
0.0
Enabled
Ɣ/Ɣ
-
Ɣ
Ɣ
6. 18
[15] Commercial/inverter switching function Sensorless vector/vector with sensor (Ɣ:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector control
PM
control
V/f Reference
Speed
control
Torque
control
H
0354
Commercial power/inverter
switching output selection
0:Disabled
1:Automatic switching in the event of a trip
2:Commercial power switching frequency setting
3:Commercial power switching frequency setting +
automatic switching in the event of a trip
1/1 0 Disabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 6. 19
H
0355
Commercial power/inverter
switching frequency
0~WN Hz 0.1/0.01 *2 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 6. 19
H
0356
Inverter
-
side switching waiting
time
0.10~10.00 sec. 0.01/0.01 *1 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 6. 19
H
0357
Commercial power
-
side
switching waiting time
0.40~10.00 sec. 0.01/0.01 0.62 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 6. 19
H
0358
Commercial power switching
frequency holding time
0.10~10.00 sec. 0.01/0.01 2.00 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 6. 19
*1: Default values vary depending on the capacity. See the table of K-48. *2: Inverter with a model number ending with -WN, HN: 60.0 -WP: 50.0
[16] PID control [1/2] Sensorless vector/vector with sensor (Ɣ:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector control
PM
control
V/f Reference
Speed
control
Torque
control
H
0359 PID control switching
0:No PID control
1:Process type PID control (temp./pressure, etc.)
operation
2:Speed type PID control (potentiometer, etc.)
operation
3:Stop retaining P control
4.
Dancer control
1/1 0 Disabled Ɣ/Ɣ - Ɣ Ɣ *1, *2
*1: For details, refer to Instruction Manual (E6581319) specified in Section 6.42. *2: For details, refer to Instruction Manual (E6581329) specified in Section 6.42.