Toshiba VF-AS1 Welding System User Manual


 
E6581301
11
K-2
2. Basic parameter [2/4] Sensorless vector/vector with sensor (Ɣ:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector control
PM
control
V/f Reference
Speed
control
Torque
control
RV 0015 V/f control mode selection
0:Constant torque characteristics
1:Voltage decrease curve
2:Automatic torque boost
3:Sensorless vector control 1 (speed)
4:Sensorless vector control 2 (speed/torque)
5:V/f 5-point setting
6:PM control
7:PG feedback control
8:PG feedback vector control
1/1 0 Disabled
-
/
-
-/-
Ɣ/-
Ɣ/-
Ɣ/-
-/-
-/-
-/Ɣ
-
/
Ɣ
-
/
-
-/-
-/-
-/-
Ɣ/-
-/-
-/-
-/-
-
/
Ɣ
-
-
-
-
-
-
Ɣ
-
-
Ɣ
Ɣ
-
-
-
Ɣ
-
-
-
5. 6
XD
0016
Manual torque boost
1
0
.0~30.0%
0.1/0.1
*1
Enabled
-
-
Ɣ
Ɣ
5. 7
XN
0014
Base frequency 1
25.0~
500
ҢҢҠҢ
Hz
0.1/0.01
*
3
Disabled
Ɣ
/
Ɣ
Ɣ
/
Ɣ
Ɣ
Ɣ
5. 8
XNX
0409 Base frequency voltage 1
200V class:50~330V
400V class:50~660V
1/0.1 *1 Disabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 5. 8
HJ
0011
Maximum frequency
30.0~500.0Hz
0.1/0.01
80.0
Disabled
Ɣ
/
Ɣ
Ɣ
/
Ɣ
Ɣ
Ɣ
5. 9
WN
0012
Upper limit frequency
0.0~
HJ
Hz
0.1/0.01
*
3
Enabled
Ɣ
/
Ɣ
-
Ɣ
Ɣ
5. 10
NN
0013
Lower limit frequency
0.0~
WN
Hz
0.1/0.01
0.0
Enabled
Ɣ
/
Ɣ
-
Ɣ
Ɣ
5. 10
CEE
0009
Acceleration time 1
0.1~6000 sec.
0.1/
0.1 *2
*1
Enabled
Ɣ
/
Ɣ
-
Ɣ
Ɣ
5. 2
FGE
0010
Deceleration time 1
0.1~6000 sec.
0.1/0.1 *2
*1
Enabled
Ɣ
/
Ɣ
-
Ɣ
Ɣ
5. 2
CXH
0213
RR
/S4
input point 2
frequency
0.0~HJ Hz 0.1/0.01 *3 Enabled Ɣ/Ɣ - Ɣ Ɣ 5. 11
CKH
0204
VI/II input point 2 frequency
0.0~
HJ
Hz
0.1/
0.01
*
3
Enabled
Ɣ
/
Ɣ
-
Ɣ
Ɣ
5. 11
UT
0018
Preset speed operation
frequency 1
NN~WN Hz 0.1/0.01 0.0 Enabled Ɣ/Ɣ - Ɣ Ɣ 5. 12
UT
0019
Preset speed operation
frequency 2
NN~WN Hz 0.1/0.01 0.0 Enabled Ɣ/Ɣ - Ɣ Ɣ 5. 12
UT
0020
Preset speed operation
frequency
3
NN~WN Hz 0.1/0.01 0.0 Enabled Ɣ/Ɣ - Ɣ Ɣ 5. 12
UT
0021
Preset speed operation
frequency 4
NN~WN Hz 0.1/0.01 0.0 Enabled Ɣ/Ɣ - Ɣ Ɣ 5. 12
UT
0022
Preset speed operation
frequency 5
NN~WN Hz 0.1/0.01 0.0 Enabled Ɣ/Ɣ - Ɣ Ɣ 5. 12
UT
0023
Preset speed op
eration
frequency 6
NN~WN Hz 0.1/0.01 0.0 Enabled Ɣ/Ɣ - Ɣ Ɣ 5. 12
UT
0024
Preset speed operation
frequency 7
NN~WN Hz 0.1/0.01 0.0 Enabled Ɣ/Ɣ - Ɣ Ɣ 5. 12
HT 0008
Forward run/reverse run
selection (operation panel
operation)
0:Forward run
1:Reverse run
2:Forward run (Forward/reverse switchable on operation
panel)
3:Reverse run (Forward/reverse switchable on
operation panel)
1/1 0 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 5. 13
*1: Default values vary depending on the capacity. See the table of K-48.
*2: Changing the parameter VR enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).
*3: Inverter with a model number ending with -WN, HN: 60.0 -WP: 50.0