Toshiba VF-AS1 Welding System User Manual


 
E6581301
L-1
12
12. Specifications
12.1 Models and their standard specifications
1) Standard specifications (small/medium capacity types)
Item Specification
Voltage class
200V class
Applicable motor (kW)
0.4 0.75 1.5 2.2 3.7/4.0 5.5 7.5 11 15 18.5 22 30 37 45
Applicable motor (HP)
0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60
Rating
Type VFAS1-
Form
2004PL 2007PL 2015PL 2022PL 2037PL 2055PL 2075PL 2110PM2150PM2185PM2220PM2300PM2370PM2450PM
Output capacity (kVA)
[Note 1]
1.1 1.8 3.0 4.2 6.7 10 13 21 25 29 34 46 55 67
Output current
(A) [Note 2]
3.0
(3.0)
4.8
(4.5)
8.0
(8.0)
11
(10.5)
17.5
(16.6)
27.5
(25.0)
33
(33)
54
(49)
66
(64)
75
(66)
88
(75)
120
(88)
144
(120)
176
(140)
Output voltage Three-phase 200V~240V (The maximum output voltage is equal to the input supply voltage.)
Overload
current rating
150%-1 minute, 165%-2 sec.
Electrical
braking
Dynamic
braking circuit
Built-in dynamic braking drive circuit
Dynamic braking
resistor
An external braking resistor (optional)
Rating: Refer to 5.19.
Power
supply
Voltage-frequency
Three-phase 200~240V-50/60Hz [Note 3]
Allowable
fluctuation
Voltage + 10% - 15% [Note 4] Frequency ±5%
Protective method
(IEC60529)
IP20 Enclosed type IP00 Open type [Note 5]
Cooling method Forced air-cooled
Cooling fan noise (dBA)
43 43 43 55 55 56 58 60 60
60 60 64 64 64
Color RAL7016
EMC filter Built-in
Basic filter (Not complies with the European EMC Directive)
DC reactor External DC reactor (option) Built-in
Item Specification
Voltage class
400V class
Applicable motor (kW)
0.75 1.5 2.2 3.7/4.0 5.5 7.5 11 15 18.5 22 30 37 45 55 75
Applicable motor (HP)
1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100
Rating
Type VFAS1-
Form 4007PL 4015PL 4022PL 4037PL 4055PL 4075PL 4110PL 4150PL 4185PL 4220PL 4300PL 4370PL 4450PL 4550PL 4750PL
Output capacity (kVA)
[Note 1]
1.8 3.1 4.4 8.0 11 13 21 25 31 37 50 60 72 88 122
Output current
(A) [Note 2]
2.3
(2.3)
4.1
(4.0)
5.8
(4.6)
10.5
(8.6)
14.3
(13)
17.6
(17)
27.7
(25)
33
(32)
41
(37)
48
(38)
66
(53)
79
(60)
94
(75)
116
(93)
160
(120)
Output voltage Three-phase 380V~480V (The maximum output voltage is equal to the input supply voltage.)
Overload
current rating
150%-1 minute, 165%-2 sec.
Electrical
braking
Dynamic
braking circuit
Built-in dynamic braking drive circuit
Dynamic braking
resistor
An external braking resistor (optional)
Rating: Refer to 5.19.
Power
supply
Voltage-frequenc
y
Three-phase 380~480V-50/60Hz [Note 3]
Allowable
fluctuation
Voltage + 10% - 15% [Note 4] Frequency ±5%
Protective method
(IEC60529)
IP20 Enclosed type IP00 Open type [Note 5]
Cooling method Forced air-cooled
Cooling fan noise (dBA)
43 43 43 55 56 56 58 60 60 60 64 64 64 64 64
Color RAL7016
EMC filter Built-in
DC reactor External DC reactor (option) Built-in
Note 1: Capacity is calculated at 220V for the 200V models and at 440V for the 400V models.
Note 2: Rated output current when the PWM carrier frequency (parameter EH) is 4kHz or less.
The values between parentheses refer to rated output currents when set to 12kHz.
Refer to 1.4.4 ”Current reduction curve” for details.
Note 3: If you are using a 200V-15kW or 400V-2.2kW inverter and the ambient temperature is 40°C or more,
decrease the PWM carrier frequency to 8kHz. Setting H to enables you to protect the overload
caused by ambient temperature described in page A-23.
An external power supply backup available (optional) (Type: CPS002Z)
Note 4: ±10% when the inverter is used continuously (load of 100%).
Note 5: HN models, 200V-18.545kW and 400V-2275kW are IP20 enclosed type.