Hitachi SJ300-037HFE Welding System User Manual


 
SJ300 Inverter
Motor Control
Accessories
5–9
Selecting a
Braking Resistor
You can add one or more resistors to your inverter configuration to increase braking torque
performance. The number of resistors and their configuration (series or parallel) depends on the
desired braking torque. The tables below list the resistor types for inverter models with internal
braking units. Tables for inverters with external braking units are on the next two pages.
Total Ohms – lists the resistance value of the resistor or, if using multiple resistors, their
combined resistance
Total Watts – lists the power dissipation of the resistor or, if using multiple resistors, their
combined power dissipation
Maximum Duty Cycle – the maximum allowable percentage of braking time over any 100-
second interval to avoid overheating the resistor(s)
Maximum braking torque – the maximum braking torque that the inverter / resistor combina-
tion can deliver
NOTE: If your application requires resistors with NEMA ratings, be sure to use the HRB type.
200V Class Dynamic Braking Resistor Selection
Max.
Braking
Torque,
%
Model
Number
SJ300
JRB Series SRB/NSRB Series HRB Series
Type
& (qty)
Total
Ohms
Total
Watts
Max.
Duty
Cycle,
%
Type
& (qty)
Total
Ohms
Total
Watts
Max.
Duty
Cycle,
%
Type
& (qty)
Total
Ohms
Total
Watts
Max.
Duty
Cycle,
%
–004LFU 120–3 50 120 1.5 300–1 50 300 7.5 HRB1 50 400 10 200
–007LFU 120–3 50 120 1.5 300–1 50 300 7.5 HRB1 50 400 10 200
–015LFU 120–4 35 120 1.0 400–1 35 400 7.5 HRB2 35 600 10 200
–022LFU 120–4 35 120 1.0 400–1 35 400 7.5 HRB2 35 600 10 160
–037LFU 120–4 35 120 1.0 400–1 35 400 7.5 HRB2 35 600 10 100
–055LFU
120–4
x (2) in
parallel
17.5 240 1.0
400–1
x (2) in
parallel
17.5 800 7.5 HRB3 17 1200 10 80
–075LFU 17.5 240 1.0 17.5 800 7.5 HRB3 17 1200 10 80
–110LFU 17.5 240 1.0 17.5 800 7.5 HRB3 17 1200 10 70
400V Class Dynamic Braking Resistor Selection
Max.
Braking
Torque,
%
Model
Number
SJ300
JRB Series SRB/NSRB Series HRB Series
Type
& (qty)
Total
Ohms
Total
Watts
Max.
Duty
Cycle,
%
Type
& (qty)
Total
Ohms
Total
Watts
Max.
Duty
Cycle,
%
Type
& (qty)
Total
Ohms
Total
Watts
Max.
Duty
Cycle,
%
–007HFU/HFE 120–2 100 120 1.5 200–2 100 200 7.5
HRB1
x (2) in
series
100 800 10 200
–015HFU/HFE 120–2 100 120 1.5 200–2 100 200 7.5 100 800 10 200
–022HFU/HFE 120–2 100 120 1.5 200–2 100 200 7.5 100 800 10 200
–040HFU/HFE
120–4
x (2) in
series
70 240 1.0
400–1
x (2) in
series
70 800 10
HRB2
x (2) in
series
70 1200 10 140
–055HFU/HFE 70 240 1.0 70 800 10 70 1200 10 120
–075HFU/HFE 70 240 1.0 70 800 10 70 1200 10 100
–110HFU/HFE 70 240 1.0 70 800 10 70 1200 10 70