The parameters in the following table adjust the input characteristics of the analog inputs.
When using the inputs to command the inverter output frequency, these parameters adjust the
starting and ending ranges for the voltage or current, as well as the output frequency range.
Related characteristic diagrams are located in
Analog Input Settings” on page 3–11.
“A” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
A101 [OI]–[L] input active
range start frequency
The output frequency corre-
sponding to the current input
range starting point.
Range is 0.00 to 400.0 Hz
✘ ✔ 00.0 00.0 00.0 Hz
>A101 INPUT-OI
EXS 0000.00Hz
A102 [OI]–[L] input active
range end frequency
The output frequency corre-
sponding to the current input
range ending point.
Range is 0.00 to 400.0 Hz
✘ ✔ 00.0 00.0 00.0 Hz
>A102 INPUT-OI
EXE 0000.00Hz
A103 [OI]–[L] input active
range start current
The starting point for the
current input range.
Range is 0 to 100%
✘ ✔ 20. 20. 20. %
>A103 INPUT-OI
EX%S 020%
A104 [OI]–[L] input active
range end current
The ending point for the
current input range.
Range is 0 to 100%
✘ ✔ 100. 100. 100. %
>A104 INPUT-OI
EX%E 100%
A105 [OI]–[L] input start
frequency enable
Two options:
00 Use A101 start value
01 Use 0Hz
✘ ✔ 01 01 01 Hz
>A105 INPUT-OI
LEVEL 0Hz
A111 [O2]–[L] input active
range start frequency
The output frequency corre-
sponding to the bipolar
voltage input range starting
point.
Range is –400. to 400. Hz
✘ ✔ 0.00 0.00 0.00 Hz
>A111 INPUT-O2
EXS +000.00Hz
A112 [O2]–[L] input active
range end frequency
The output frequency corre-
sponding to the bipolar
voltage input range ending
point.
Range is –400. to 400. Hz
✘ ✔ 0.00 0.00 0.00 Hz
>A112 INPUT-O2
EXE +000.00Hz
A113 [O2]–[L] input active
range start voltage
The starting point for the
bipolar voltage input range.
Range is –100 to 100%
✘ ✔ -100. -100. -100. %
>A113 INPUT-O2
EX%S -100%
A114 [O2]–[L] input active
range end voltage
The ending point for the
bipolar voltage input range.
Range is –100 to 100%
✘ ✔ 100. 100. 100. %
>A114 INPUT-O2
EX%E +100%