SJ300 Inverter
Inverter Mounting
and Installation
2–7
Step 2: To summarize the caution messages—you will need to find a solid, non-flammable,
vertical surface that is in a relatively clean and dry environment. In order to ensure enough
room for air circulation around the inverter to aid in cooling, maintain the specified clearance
around the inverter specified in the diagram.
CAUTION: Be sure to maintain the specified clearance area around the inverter and to provide
adequate ventilation. Otherwise, the inverter may overheat and cause equipment damage or fire.
Step 3: Before proceeding to the wiring section, it’s a
good time to temporarily cover the inverter’s ventila-
tion openings. Paper and masking tape are all that is
needed. This will prevent harmful debris such as wire
clippings and metal shavings from entering the
inverter during installation.
Please observe this checklist while mounting the
inverter:
1. The ambient temperature must be in the range of
-10 to 40°C. If the range will be up to 50°C
(maximum rating), you will need to refer to
“
Derating Curves” on page 1–11.
2. Keep any other heat-producing equipment as far
away from the inverter as possible.
3. When installing the inverter in an enclosure,
maintain the clearance around the inverter and
verify that its ambient temperature is within speci-
fication when the enclosure door is closed.
4. Do not open the main front panel door at any time
during operation.
2
Ensure Adequate
Ventilation
SJ300
5 cm (1.97”)
minimum
10 cm (3.94”)
minimum
5 cm (1.97”)
minimum
10 cm (3.94”)
minimum
Exhaust
Air intake
Clear area
3
Keep Debris Out
of Inverter Vents
Cover the ventilation slots,
both sides
C
over
th
e
f
an ou
tl
e
t
ven
t
s