SJ300 Inverter
Configuring Drive
Parameters
3–13
Multi-speed and
Jog Frequency
Settings
The SJ300 inverter has the capability to store and output up to 16 preset frequencies to the
motor (A020 to A035). As in traditional motion terminology, we call this multi-speed profile
capability. These preset frequencies are selected by means of digital inputs to the inverter. The
inverter applies the current acceleration or deceleration setting to change from the current
output frequency to the new one. The first multi-speed setting is duplicated for the second
motor settings (the remaining 15 multi-speeds apply only to the first motor).
The jog speed setting is used whenever the Jog command is active. The jog speed setting range
is arbitrarily limited to 10 Hz to provide safety during manual operation. The acceleration to the
jog frequency is instantaneous, but you can choose from six modes for the best method for
stopping the jog operation.
“A” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
A019 Multi-speed operation
selection
Two options; select codes:
00 Binary; up to 16-stage
speed using 4 intelligent
terminals
01 Single-bit; up to 8-stage
speed using 7 intelligent
terminals
✘ ✘ 00 00 00 —
>A019 SPEED
SELECT BINARY
A020 Multi-speed frequency
setting
Defines the first speed of a
multi-speed profile, range is
0 to 360 Hz
A020 = Speed 1 (1st motor)
✔ ✔ 0.00 0.00 0.00 Hz
>A020 SPEED
FS 0000.00Hz
A220 Multi-speed frequency
setting, 2nd motor
Defines the first speed of a
multi-speed profile for 2nd
motor, range is 0 to 360 Hz
A220 = Speed 1 (2nd motor)
✔ ✔ 0.00 0.00 0.00 Hz
>A220 SPEED
2FS 0000.00Hz
A320 Multi-speed frequency
setting, 3rd motor
Defines the first speed of a
multi-speed profile for 3rd
motor, range is 0 to 360 Hz
A320 = Speed 1 (3rd motor)
✔ ✔ 0.00 0.00 0.00 Hz
>A320 SPEED
3FS 0000.00Hz
A021
to
A035
Multi-speed frequency
settings
(for both motors)
Defines 15 more speeds,
range is 0 to 360 Hz.
A021 = Speed 2...
A035 = Speed 16
✔ ✔ 0.00 0.00 0.00 Hz
>A021 SPEED
01S 0000.00Hz
A038 Jog frequency setting Defines limited speed for
jog, range is 0.5 to 9.99 Hz
✔ ✔ 1.00 1.00 1.00 Hz
>A038 Jogging
F 01.00Hz
A039 Jog stop mode Define how end of jog stops
the motor; six options:
00 Free-run stop, jogging
disabled during motor
run
01 Controlled deceleration,
jogging disabled during
motor run
02 DC braking to stop,
jogging disabled during
motor run
03 Free-run stop, jogging
always enabled
04 Controlled deceleration,
jogging always enabled
05 DC braking to stop,
jogging always enabled
✘ ✔ 00 00 00 —
>A039 Jogging
Mode FRS