SJ300 Inverter
Appendix C
C–5
A056 DC braking / edge or level detection
for [DB] input
01 01 01
A057 DC braking force for starting 0. 0. 0.
A058 DC braking time for starting 0.0 0.0 0.0
A059 DC braking carrier frequency setting 5.0 5.0 5.0
A061 Frequency upper limit setting 0.00 0.00 0.00
A0261 Frequency upper limit setting, 2nd
motor
0.00 0.00 0.00
A062 Frequency lower limit setting 0.00 0.00 0.00
A0262 Frequency lower limit setting, 2nd
motor
0.00 0.00 0.00
A063,
A065,
A067
Jump (center) frequency setting 0.00 0.00 0.00
A064,
A066,
A068
Jump (hysteresis) frequency width
setting
0.50 0.50 0.50
A069 Acceleration stop frequency setting 0.00 0.00 0.00
A070 Acceleration stop time frequency
setting
0.0 0.0 0.0
A071 PID Function Enable 00 00 00
A072 PID proportional gain 1.0 1.0 1.0
A073 PID integral time constant 1.0 1.0 1.0
A074 PID derivative gain 0.0 0.0 0.0
A075 PV scale conversion 1.00 1.00 1.00
A076 PV source setting 00 00 00
A081 AVR function select 00 00 00
A082 AVR voltage select 230/400 230/460 200/400
A085 Operation mode
selection
00 00 00
A086 Energy saving mode tuning 50.0 50.0 50.0
A092 Acceleration (2) time setting 15.0 15.0 15.0
A292 Acceleration (2) time setting, 2nd
motor
15.0 15.0 15.0
A392 Acceleration (2) time setting, 3rd
motor
15.0 15.0 15.0
A093 Deceleration (2) time setting 15.0 15.0 15.0
“A” Group Parameters Default Setting
User
Setting
Func.
Code
Name
-FE (Europe) -FU (USA) -FR (Japan)