Hitachi SJ300-037HFE Welding System User Manual


 
“F” Group: Main Profile Parameters
Configuring Drive
Parameters
3–8
“F” Group: Main Profile Parameters
The basic frequency (speed) profile is
defined by parameters contained in the
“F” Group as shown to the right. The
output frequency is set in Hz, but accel-
eration and deceleration are specified
seconds (the time to ramp from zero to
maximum frequency, or from maximum
frequency to zero). The motor direction
parameter determines whether the
keypad Run key produces a FW or RV
command. This parameter does not
affect the [FW] terminal or [RV] intelligent terminal function, which you configure separately.
Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the main
profile. Accel and decel values for an alternative profile are specified by using parameters Ax92
through Ax93. The motor direction selection (F004) determines the direction of rotation as
commanded only from the keypad. This setting applies to any motor profile (1st, 2nd, or 3rd) in
use at a particular time.
Output
frequency
F001
F002 F003
t
“F” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
F001 Output frequency
setting
Standard default target
frequency that determines
constant motor speed
Range is 0 to 400 Hz
✔ ✔ 0.00 0.00 0.00 Hz
>F001 SET-Freq.
TM 0000.00Hz
2FS 0000.00Hz
3FS 0000.00Hz
TM 0000.00Hz
JG 0000.00Hz
1S 0000.00Hz
15S 0000.00Hz
OP1 0000.00Hz
OP2 0000.00Hz
RS485 0000.00Hz
F002 Acceleration (1) time
setting
Standard default accelera-
tion
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0 sec.
>F002 ACCEL
TIME1 0030.00s
F202 Acceleration (1) time
setting, 2nd motor
Standard default accelera-
tion, 2nd motor
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0 sec.
>F202 2ACCEL
TIME1 0030.00s
F302 Acceleration (1) time
setting, 3rd motor
Standard default accelera-
tion, 3rd motor
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0 sec.
>F302 3ACCEL
TIME1 0030.00s
F003 Deceleration (1) time
setting
Standard default decelera-
tion
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0 sec.
>F003 DECEL
TIME1 0030.00s
F203 Deceleration (1) time
setting, 2nd motor
Standard default decelera-
tion, 2nd motor
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0 sec.
>F203 2DECEL
TIME1 0030.00s
F303 Deceleration (1) time
setting, 3rd motor
Standard default decelera-
tion, 3rd motor
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0 sec.
>F303 3DECEL
TIME1 0030.00s
F004 Keypad Run key routing Two options; select codes:
00 Forward
01 Reverse
✘ ✘ 00 00 00
>F004 DIG-RUN
SELECT FW