Honeywell DR4300 Work Light User Manual


 
Configuration, Startup, and Operation
of Recorder with Display
12/03 DR4300 Circular Chart Recorder Product Manual 115
4.3.20 Lock Out Parameter Set Up Group
Introduction
This is the parameter used to lockout any unauthorized changes to the recorder’s configuration, calibration,
and pen alignment parameters. Calibration group functions are described in Section 5 – Input and Output
Calibration for Recorder with Display. Pen alignment group functions are described in Section 8
Troubleshooting and Pen Alignment for Recorder with Display.
Set this group last
Because this group contains functions that have to do with security and lockout, we recommend that you
configure this group last, after all the other configuration data has been entered.
Lockout group prompts
Table 4-18 lists the function prompt in the lock out set up group.
Press SETUP
key until “LOCK” appears in the lower display.
Press FUNC
key to select the parameter.
Table 4-18 Lockout Parameter Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
LOCK
LOCK limits access to one or more types of set up
groups.
Do not configure until all configuration is
complete.
NONE [factory setting]
NO LOCKOUT—All groups read/write.
CAL
CAL—Locks out calibration and pen alignment groups;
they will not even be displayed.
All other groups are
available for read/write.
CONF
CONF—Tuning and cycle parameters are read/write. All
other configuration groups (except lock) are read only.
Calibration and pen alignment groups are not displayed.
FULL
FULL— All configuration groups (except lock) are read
only. Calibration and pen alignment groups are not
displayed.
ATTENTION
The Lock function cannot be changed when the RUN/SETUP switch is in the "SETUP" position, making it
usable as a physical lockout. Whatever lockout level is selected, it is protected as long as the switch is in
the SETUP position.