Honeywell DR4300 Work Light User Manual


 
DR4300 Circular Chart Recorder
86 DR4300 Circular Chart Recorder Product Manual 12/03
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
IN TYP
* IEC Alpha =
0.00385
**IEC Alpha =
0.00391
***These input
selections are not
available on Limit
Control units.
B
EH
EL
JH
JL
KH
KL
NNM
NIC
R
S
TH
TL
W
100 H*
[factory setting]
100 L*
100 T**
4-20***
0-20***
10m***
100m***
200m***
0-1***
0-2***
1-5***
0-5***
0-10***
2-10***
INPUT ACTUATION TYPE—This selection specifies what actuation
you are going to use for the input. Be sure that the values
configured for the high and low chart range, alarm setpoint, etc. are
within the measuring range for the selected actuation type.
B thermocouple 105 to 3300°F 41 to 1815°C
E thermocouple high –454 to 1832°F –270 to 1000°C
E thermocouple low –200 to 1100°F –129 to 593°C
J thermocouple high 0 to 1600°F –18 to 871°C
J thermocouple low 20 to 770°F –7 to 410°C
K thermocouple high –320 to 2500°F –196 to 1371°C
K thermocouple low –20 to 1000°F –29 to 538°C
NiNiMo thermocouple 32 to 2500°F 0 to 1371°C
Nicrosil-Nisil
thermocouple 0 to 2372°F –18.8 to 1300°C
R thermocouple 0 to 3100°F –18 to 1704°C
S thermocouple 0 to 3100°F –18 to 1704°C
T thermocouple high –420 to 700°F –251 to 371°C
T thermocouple low –200 to 600°F –129 to 316°C
W thermocouple 0 to 4200°F –18 to 2316°C
100 Ohm–RTD (high) –300 to 900°F –184 to 482°C
100 Ohm-RTD (low) –130 to 392°F –90 to 200°C
100 Ohm-RTD (special) –238 to 482°F –150 to 250°C
4 to 20 Milliamps
0 to 20 Milliamps
0 to 10 Millivolts
0 to 100 Millivolts
0 to 200 Millivolts
0 to 1 Volt
0 to 2 Volts
1 to 5 Volts
0 to 5 Volts
0 to 10 Volts
2 to 10 Volts
XMITTR
Lin
[factory setting]
Srt
Transmitter Input Type—Use this parameter to specify whether
the input should be used as the PV without characterization (linear)
or the square root of the input should be used as the PV.
Linear—No characterization applied to input.
Square Root—PV is the square root of input. For example:
suppose the linear input range is 0 to 5000 and the input type is 0 to
5 volts. Then if input = 2.5 V = 50 %,
.50 .7071 70.71%