Step Action/Result Graphic
9
At the conclusion of the test turn off the power to the
recorder.
10 Being careful of the shock hazard at TB1, place run
switch SW5 to the run position (toward the bottom of the
board) on each PCA.
11
Set configuration switches on the PCA for each pen back
to the settings noted in Step 4.
12
Secure the chart plate in the operational position.
13
To resume normal operation leave SW5 in the run
position and power up the recorder.
Chart step pattern
Figure 3-4 is a typical chart step pattern generated by the recorder in the step test.
24141