Be sure that thermocouple
extension wire matches
thermocouple type
Keep resistance of all wires equal
Use 18 gauge copper wire for lengths up
to 150 feet.
For two wire RTD jumper terminal
negative (-) to R.
Thermocouple
RTD
mA, mV or Volt
mA, mV or
Volt source
TB2
TB2
TB2
+
RTD
+
R
+
R
T/C
R
24086
Main PCA
Pen 2
Main PCA
Pen 1
Many 3-wire RTDs use color coded
wires. One wire is a different color than
the other two. The single wire is usually
the positive connection
J
K
T
R
S
E
B
+ White
-
Red
-
Red
-
Red
-
Red
-
Red
-
Red
-
Red
+ Yellow
+ Blue
+ Black
+ Black
+ Purple
+ Gray
7
TB2
TB1
7
TB2
TB1
N
-
Red
+ Orange
100 ohm maximum lead resistance
Standard used as color
reference ANSI MC96.1
Figure 2-11 Analog Input Wiring