DR4300 Circular Chart Recorder
200 DR4300 Circular Chart Recorder Product Manual 12/03
A.2 Typical Reference Accuracy
Table A-1 Typical Reference Accuracy
Types of Input
Actuations
Range Reference
Accuracy*
with
Field
Calibration
Factory
Accuracy*
Temp Stability
± Degrees
Error Per 1 Degree
T
°F °C ± °F ± °C ± °F ± °C
Thermocouples
B
105 to 3300
150 to 500
500 to 1000
1000 to 3300
41 to 1816
66 to 260
260 to 538
538 to 1815
28.0
6.0
3.0
16.0
3.3
1.7
37
18
21
10
4.00
1.00
0.40
E
–454 to 1832
–454 to –202
–202 to 1832
–270 to 1000
–270 to –130
–130 to 1000
36.0
2.0
20.0
1.1
79
14
44
8
1.40
0.70
E (low)
–200 to 1100 –129 to 593
1.0 0.6 11 6 0.40
J
0 to 1600 –18 to 871
1.6 0.9 7 4 0.15
J (low)
20 to 770 –7 to 410
0.8 0.5 6 3 0.08
K
–320 to 2500 –196 to 1371
2.4 1.4 9 5 0.15
K (low)
–20 to 1000` –29 to 538
1.0 0.6 7 4 0.10
Ni-Ni Moly
32 to 2500
32 to 500
500 to 2500
0 to 1317
0 to 260
260 to 1371
1.5
1.0
0.8
0.6
12
9
7
5
0.21
0.14
Nicrosil-Nisil
0 to 2372 –18 to 1200
2.1 1.2 11 6 0.20
R
0 to 3100
0 to 500
500 to 3100
–18 to 1704
–18 to 260
260 to 1704
4.0
2.0
2.2
1.1
26
13
14
7
0.50
0.21
S
0 to 3100
0 to 500
500 to 3100
–18 to 1704
–18 to 260
260 to 1704
4.0
2.0
2.2
1.1
23
13
13
7
0.50
0.21
T
–420 to 700 –251 to 371
1.6 0.9 13 7 0.15
T (low)
–200 to 600 –129 to 316
0.8 0.5 7 4 0.15
W5W26
0 to 4200
0 to 600
600 to 3600
3600 to 4200
–18 to 2316
–18 to 316
316 to 1982
1982 to 2316
2.8
2.6
3.2
1.6
1.5
1.8
19
13
27
11
7
15
1.00
0.50
0.20
RTD
Platinum
100 ohms**
100 ohms
(low)**
100 ohms (T)***
–300 to 900
–130 to 392
–238 to 482
–184 to 482
–90 to 200
–150 to 250
0.8
0.6
0.6
0.5
0.3
0.3
4
3
3
2
2
2
0.15
0.15
0.15
*Includes reference junction calibration of ± 0.01 degrees using the standard "ice bath" method of calibration. Factory accuracy at
reference ± 1.2 °F. Note that factory accuracy may have typical variations of ± 150 microvolts or ± 0.6 ohms for RTDs which
means field calibration may be required to achieve stated accuracy.
**IEC Alpha = 0.00385
***Alpha = 0.00391