Topcon A2677 Paint Sprayer User Manual


 
10-3
A2677 Rev 1.5
X20 Sprayer Reference Manual
Calibrating the Pressure Sensor
Before calibrating the Pressure Sensor make sure you have selected
which Type of Pressure Sensor is connected to the system (page
8-38) and what Calibration Method you are going to use (page
8-43).
S1. elect RESTORE FACTORY DEFAULTS at the bottom of
Tank Pressure window (Figure 10-1 on page 10-1)
Select 2. CALIBRATE SENSOR in the Tank Pressure
window (Figure 10-1 on page 10-1)
Follow the on screen directions to calibrate the Pressure 3.
Sensor
To calibrate the Pressure Sensor the console will take a zero
reading of the pressure when the pump is switched OFF.
Then another reading of the pressure when the pump is at
operating pressure. You will enter the actual pressure as read
from a Glass Pressure Gauge, using the screen keyboard.
Once the calibration is complete, check the Pressure Readout 4.
from the Working screen and compare it against the Glass
Pressure Gauge.
If the difference is more than 10% then make note of the
Actual Pressure and the Pressure Readout from the Working
screen.
A Manual Pressure gauge must be fitted to the
system to determine the actual pressure for
calibration purposes.
NOTICE
NOTICE