ProWORX 32 Utilities
222
372 SPU 780 01EMAN May 2002
Working with
Routing Paths
In the BM85 Configuration Dialog:
Communicating
with the BM85
If you are having trouble communicating with the BM85:
To: Action:
Add a routing path Select a table from the Table drop-down box, and an address
from the Address drop-down box. Enter a routing path in the
Installed Routing Path box. Click Add.
Remove a routing path Select a routing path from the Address list box and press
DELETE or click Remove.
Step Action
1 Make sure the COM port selected is plugged into the BM85.
2 Make sure the port on the BM85 you are plugged into is in configure mode. Set
MODBUS Port Configuration switches on the BM85 to CONFIGURE, PORT 1,
9600 BAUD, NO PARITY, 1 STOP BIT (All off).