Troubleshooting
372 SPU 780 01EMAN May 2002 299
S901/J200 Status
Word 68 Hex
(104 Decimal)
This word shows the status of the remote I/O processor. The upper 4 bits should be
zero under normal operating conditions. An error indicates a failure in the remote I/
O processor.
RIO error status:
Binary Number Description
000 RIO did not respond
001 No response on loopback
010 Failed loopback data check
011 Timeout while awaiting response
100 RIO did not accept all of message
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
RIO error status
1 = S901 (J200) memory failure
1 = S901 (J200) loopback failure
1 = S901 (J200) timeout
1 = S901 (J200) bad