Schneider Electric 372 SPU 780 01EMAN Welding System User Manual


 
Troubleshooting
290
372 SPU 780 01EMAN May 2002
S911 Hot Standby Status (S908)
Word 66 Hex
(102 Decimal)
The hot standby status is valid if a redundancy system is present. It shows if the unit
is reporting present and healthy and the word also indicates if the unit is the primary
or secondary controller.
Word 4 (4xxxx + 3) - S911/R911 Hot Standby Status
System State:
Binary Number Description
01 Offline
10 Primary
11 Secondary
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
S911/R911 present and healthy
0 = Controller set to A
1 = Controller set to B
0 = Controllers logic matches
1 = Controllers logic mismatches
Remote system state
Local system state